Diesel tanks – TANK FUEL GE without an erogation group, built in conformity to present normative, for fuelling electricity generators. They are equipped with a collection basin able to hold 110% of total quantity of the tank. Service ladder, erogation system protection roof (as foreseen by the Ministry Decree). The tanks and the collection basins are made of carbon steel of S235JR quality according to the normative UNI EN 10025-2 and are treated externally with two coats of primer and a following finish of two coats of metallic grey synthetic enamel. They are supplied with a discharge or cleaning hose with a galvanized plug of 1 inch upper hose for a level probe l , attachment for the connection of the earth cable, a gangway 400mm in diameter complete of bolts and anti petrol gasket with an opening of 3 inch with a bayonet lockable quick stopper and a check valve with a 90% load , exhaust with a terminal fire barrier in brass, indicator of mechanic level indicator with a float, electric panel and level probe, aspiration tubes with a no return valve with a calibrated spring, spherical valve for lockage(useful for maintenance operations and a galvanized TEE connection.Capacity liters: | 1.200 | 2.000 | 3.000 | 5.000 | 7.000 | 9.000 |
* The protection roof is optional and it is made of a galvanized frame covered by galvanized sheet. It constitutes of four poles placed for the insert in the support for the collection basin, upper frame and covering sheet. Each diesel tank –TANK FUEL GE is provided with the following documents:- A certificate of approval for usage - Metric chart;